| analogue input number |
8 |
| Addressing requirement |
10 input words |
| Analogue input type |
Thermocouple: - 210...760 °C for thermocouple J Thermocouple: - 270...1000 °C for thermocouple E Thermocouple: - 270...1370 °C for thermocouple K Thermocouple: - 270...400 °C for thermocouple T Thermocouple: - 50...1665 °C for thermocouple R Thermocouple: - 50...1665 °C for thermocouple S |
| Analogue input resolution |
16 bits |
| Absolute accuracy error |
+/- 2 °C plus + 0.1 % of reading thermocouple E +/- 2 °C plus + 0.1 % of reading thermocouple J +/- 2 °C plus + 0.1 % of reading thermocouple K +/- 2 °C plus + 0.1 % of reading thermocouple T +/- 4 °C plus + 0.1 % of reading thermocouple R +/- 4 °C plus + 0.1 % of reading thermocouple S |
| Linearity error |
1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C |
| Accuracy drift according to temperature |
0.15 µV/°C + 0.0015 % of reading/°C max low level voltage |
| Common mode rejection |
> - 120 dB 50/60 Hz |
| Isolation between channels and bus |
1780 V AC for 60 s 2500 V DC for 60 s |
| Isolation between channels |
300 V DC 220 V AC |
| Update time |
1000 ms |
| Fault type |
Broken wire Overtacking scale |
| Marking |
CE |
| Cold junction compensation |
Internal 0…60 °C |
| Local signalling |
1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 8 LEDs (green) for channel is turned on 8 LEDs (red) for channel fault |
| Bus current requirement |
280 mA |
| Power dissipation in W |
1.5 W |
| module format |
Standard |
| Net weight |
0.3 kg |